These two terms are confused more than any other pair in cable procurement — and the confusion is expensive. A cable that stops fire spreading will die in the fire; a cable that survives the fire may happily spread flame along a cable tray. Flame retardant and fire resistant answer two different questions, are tested by two different IEC families, and are built with different constructions. This guide settles the difference once, and shows how to specify each without ambiguity.
| Flame Retardant | Fire Resistant | |
|---|---|---|
| What it does | Does not propagate flame along the cable | Keeps circuits working during fire |
| Test standard | IEC 60332 | IEC 60331 |
| Question answered | Will the fire spread along this cable? | Will the circuit survive the fire? |
| Key construction | Flame-quenching halogen free compounds | Mica glass tape layer under the insulation |
| Typical marking | SC / LSHF types (IEC 60332-3-22 Cat. A) | NSC / NC types (IEC 60331) |
| Installed together? | Yes — fire resistant cables are also flame retardant; the reverse is not true | |
A flame retardant cable is designed not to feed a fire. When exposed to flame it chars and self-extinguishes instead of dripping burning material or carrying flame along its length. Performance is verified by the IEC 60332 family: the single wire test (60332-1) screens materials, while the bunched categories (60332-3-22 to -25) test the behavior that matters in real installations, where cables burn in trays and bunches. On ships, the "SC" LSHF designation on shipboard types points to Category A bunched performance as standard practice.
What flame retardance does not promise: that the cable works after or during the fire. The conductors may be intact when the flame moves on — or not. Retardance is about the fire's journey, not the circuit's survival.
A fire resistant cable is engineered to keep carrying current while the fire burns around it. The enabling technology is a mica glass tape wrapped over the conductor under the normal insulation: when polymer insulation burns or melts, the mica layer fuses into a continuous insulating ceramic barrier that keeps phases separated and the circuit alive at furnace temperatures of 830°C and above, with mechanical shock, for times specified per the installation — commonly 30, 60, 90 or 120 minutes under IEC 60331-1 and IEC 60331-2.
Circuit integrity is what emergency systems need: fire pumps, emergency lighting, alarm and emergency shutdown circuits, emergency generators and their feeders. If the cable fails, the emergency system is dead exactly when it is needed. That is why class rules and SOLAS require fire resistant types on these circuits, and why a type test certificate to IEC 60331 is a procurement document, not a marketing claim.
In practice the two properties stack. A fire resistant shipboard cable carries the same halogen free, Category A flame retardant sheath as its SC sibling — fire resistance is added on top of retardance, not instead of it. Specification suffixes reflect the stack: SC marks flame retardant halogen free low smoke; NSC or NC marks the fire resistant version of the same type. When you specify NSC, you are buying both behaviors in one cable. DNV Type Approval TAE000050C covers exactly these NSC types — CJ85/NSC, CJ86/NSC, CJ95/NSC and CJ96/NSC — with IEC 60331-1/2 circuit integrity testing to 830°C for 120 minutes, while TAE000050D covers the SC flame retardant versions of the same family.
| Circuit / area | Required behavior | Why |
|---|---|---|
| General power, lighting, distribution | Flame retardant (SC) | Stop the fire travelling along cable routes |
| Fire pumps, emergency lighting, alarms, ESD | Fire resistant (NSC/NC) | Circuit must survive the fire it is fighting |
| Emergency generator and switchboard feeders | Fire resistant | Source power must outlast the incident |
| Accommodation and control rooms | Flame retardant LSHF minimum | Personnel smoke protection plus spread control |
| Drilling derrick emergency systems | Fire resistant, mud resistant where exposed | Combined chemical and fire survival per zone |
Specifying fire resistant where flame retardant suffices. NSC types cost more and bend less happily; using them on every circuit wastes budget without safety benefit.
Specifying flame retardant where fire resistance is mandatory. This fails survey and, more importantly, disables emergency systems in a real fire.
Assuming "fire rated" language is self-defining. "Fire rated", "fire proof" and "flame proof" in datasheets often conceal which test was actually passed. Demand the IEC part number: 60332 for retardance, 60331 for resistance.
Ignoring the survival time. IEC 60331 reports state minutes — 30, 60, 90 or 120. Emergency systems sized for 120 minutes fail their design basis if the cable delivers 30.
Mixing building CPR classes with IEC families. Euroclasses such as B2ca describe building fire behavior, not circuit integrity; quoting them in marine documentation creates confusion at class survey.
Write the requirement as three lines: the fire behavior (IEC 60332-3-22 Category A), the circuit integrity where required (IEC 60331-1 or -2 with minutes), and the type designation from the standard family — for example "CJ95/NSC 3x25+1x16 per IEC 60092-353 with IEC 60331-1 120 min". This leaves a supplier no room to substitute a flame retardant-only type on an emergency circuit.
IEC 60332 flame retardant test guide — the spread side of the story
IEC 60092 Series Guide — shipboard standard family overview
IEC 60092-353 — low voltage power cable construction
NEK 606 — offshore mud resistance, frequently combined with NSC types in drilling zones
DNV Type Approval TAE000050C — NSC fire resistant shipboard power cable types
Shipbuilding cable solutions — where fire resistant circuits concentrate on vessels
Q1: Can a cable be flame retardant but not fire resistant?
Yes — that is the SC type. It will not spread flame but its circuits fail when the fire reaches it. Most general power cables are exactly this, correctly.
Q2: Can a cable be fire resistant but not flame retardant?
Practically no in modern marine practice. Fire resistant types are built on the halogen free flame retardant platform, so NSC types carry both. A bare fire resistant claim without a 60332 category in the datasheet is a red flag, not a feature.
Q3: What does 830°C for 120 minutes mean?
It is the IEC 60331-1 test regime: the cable is exposed to a flame at a minimum 830°C while carrying rated voltage, with mechanical shock applied, for 120 minutes — and must maintain circuit integrity throughout. It simulates a real compartment fire, not a bunsen burner.
Q4: Is mica tape the only way to achieve fire resistance?
For polymeric insulated power and control cables, the mica glass tape barrier is the established technology. Mineral insulated copper sheathed cables achieve survival differently and live in different standard families; for shipboard types, mica under XLPE or EPR is the qualified route.
Q5: How do I confirm which behavior my project specification actually needs?
Trace each circuit to its function: circuits whose failure endangers life or mission continuity — firefighting, alarms, emergency power, shutdown — need IEC 60331 with a stated duration. Everything else needs IEC 60332 Category A. Send your cable schedule through the contact page and we flag each line.
Send your cable schedule or single line enquiry through the contact page. We mark each line flame retardant or fire resistant with the test category and duration, confirm NSC type availability from type approval documents, and return TDS references with the quotation.